Inlet Temperature versus Airflow Requirement in Server

The following tables provide the required airflow rate and airflow speed to the U50/U50 LV card under various operating conditions. In these tables, the term load refers to the total power drawn by the card.

Note: In the following tables, the term load refers to the total thermal power dissipation of the card.
Table 1. Specification for the U50/U50 LV Card at Sea Level for 85°C Optical with ~63W Load
Inlet Temperature versus Airflow Requirement of PCIe Card Slot (19.51 mm x 56.15 mm) at Sea Level for 85°C Optical
Inlet Temperature to the Card (°C) Linear Feet per Minute (LFM) Cubic Feet per Minute (CFM) Pressure (inwg)
5 160 1.9 0.07
10 170 2.0 0.07
15 180 2.1 0.08
20 200 2.4 0.09
25 260 3.1 0.13
30 300 3.5 0.15
35 390 4.6 0.22
40 520 6.1 0.35
45 680 8.0 0.53
50 870 10.3 0.79
55 (not supported) 1000 11.8 1.00
Table 2. Specification for the U50/U50 LV Card at Sea Level for 70°C Optical with ~63W Load
Inlet Temperature versus Airflow Requirement of PCIe Card Slot (19.51 mm x 56.15 mm) at Sea Level for 70°C Optical
Inlet Temperature to the Card (°C) Linear Feet per Minute (LFM) Cubic Feet per Minute (CFM) Pressure (inwg)
5 160 1.9 0.07
10 170 2.0 0.07
15 180 2.1 0.08
20 200 2.4 0.09
25 260 3.1 0.13
30 300 3.5 0.15
35 390 4.6 0.22
40 520 6.1 0.35
45 680 8.0 0.53
50 870 10.3 0.79
55 (not supported) 1000 11.8 1.00
Table 3. Specification for the U50/U50 LV Card at 1200m above Sea Level for 85°C Optical with ~63W Load
Inlet Temperature versus Airflow Requirement of PCIe Card Slot (19.51 mm x 56.15 mm) at 1200m above Sea Level for 85°C Optical
Inlet Temperature to the Card (°C) Linear Feet per Minute (LFM) Cubic Feet per Minute (CFM) Pressure (inwg)
5 170 2.0 0.07
10 180 2.1 0.08
15 200 2.4 0.09
20 210 2.5 0.09
25 280 3.3 0.14
30 320 3.8 0.17
35 420 5.0 0.25
40 560 6.6 0.39
45 730 8.6 0.59
50 930 11.0 0.88
55 (not supported) 1080 12.7 1.14
Table 4. Specification for the U50/U50 LV Card at 1200m above Sea Level for 70°C Optical with ~63W Load
Inlet Temperature versus Airflow Requirement of PCIe Card Slot (19.51 mm x 56.15 mm) at 1200m above Sea Level for 70°C Optical
Inlet Temperature to the Card (°C) Linear Feet per Minute (LFM) Cubic Feet per Minute (CFM) Pressure (inwg)
5 170 2.0 0.07
10 180 2.1 0.08
15 200 2.4 0.09
20 210 2.5 0.09
25 280 3.3 0.14
30 320 3.8 0.17
35 420 5.0 0.25
40 560 6.6 0.39
45 730 8.6 0.59
50 930 11.0 0.88
55 (not supported) 1080 12.7 1.14