The following tables provide the required airflow rate and airflow speed to the T2 Telco accelerator card under various operating conditions.

Table 1. T2 Normal Flow (Exhaust Air from I/O Bracket) at Sea Level
Inlet Temperature versus Airflow Requirement out of I/O Bracket for PCIe Card Slot (56.51 mm x 20.33 mm) at Sea Level for 50 W Total Card Power
Inlet Temperature to the Card I/O Bracket (70°C)
CFM LFM Static Pressure
25 1.7 140 0.10
30 2.0 160 0.11
35 2.3 190 0.14
40 2.8 230 0.17
45 3.7 300 0.24
50 5.1 410 0.37
55 7.8 630 0.68
Table 2. T2 Normal Flow (Exhaust Air from I/O Bracket) at 1800 m above Sea Level
Inlet Temperature versus Airflow Requirement out of I/O Bracket for PCIe Card Slot (56.51 mm x 20.33 mm) at 1800 m above Sea Level for 50 W Total Card Power
Inlet Temperature to the Card CFM LFM Static Pressure
25 1.9 150 0.10
30 2.2 180 0.13
35 2.6 210 0.16
40 3.2 260 0.20
45 4.2 340 0.29
50 5.8 470 0.45
55 8.8 710 0.82
Table 3. T2 Reverse Flow (Inlet Air from I/O Bracket) at Sea Level
Inlet Temperature versus Airflow Requirement into I/O Bracket for PCIe Card Slot (66.87 mm x 13.18 mm) at Sea Level for 50 W Total Card Power
Inlet Temperature to the Card I/O Bracket (70°C)
CFM LFM Static Pressure
25 0.9 100 0.08
30 1.1 120 0.09
35 1.3 140 0.11
40 1.5 160 0.13
45 1.9 200 0.17
50 2.3 240 0.22
55 2.9 310 0.3
Table 4. T2 Reverse Flow (Inlet Air from I/O Bracket) at 1800 m above Sea Level
Inlet Temperature versus Airflow Requirement into I/O Bracket for PCIe Card Slot (66.87 mm x 13.18 mm) at 1800 m above Sea Level for 50 W Total Card Power
Inlet Temperature to the Card CFM LFM Static Pressure
25 1.0 110 0.09
30 1.2 130 0.10
35 1.4 150 0.12
40 1.7 180 0.15
45 2.1 220 0.19
50 2.6 270 0.25
55 3.3 350 0.35